Numerical Modeling of Indoor Environment with a Ceiling Fan and an Upper-Room Ultraviolet Germicidal Irradiation System.

Building and environment ·Vol. 72 ·2014-02-00 ·页码 116-124

Zhu S, Srebric J, Rudnick SN, Vincent RL, Nardell EA

Abstract

This study proposes a numerical modeling method for the indoor environment with ceiling fans and upper-room ultraviolet germicidal irradiation (UR-UVGI) fixtures. The numerical modeling deployed steady-state Computational Fluid Dynamics (CFD) with a rotating reference frame to simulate the rotation of fan blades. CFD was validated with experimental data of velocity field and fraction of microorganism remaining at the exhaust diffuser. The fraction of microorganism remaining represented the ratio of the concentration of airborne microorganisms measured with UVGI turned on to the one measured with UVGI turned off. According to the validation results, the CFD model correctly reproduced the air movement induced by the rotation of ceiling fan. When the ambient ventilation rate was 2 ACH (air changes per hour) or 6 ACH, the CFD model accurately predicted the average vertical speeds in the section 2.44 m above the floor with the errors less than 10%, regardless of the ceiling fan's rotational direction or speed. In addition, the simulation results showed that the fraction of microorganism remaining increased with the ambient air exchange rate when the fan blew air downward with a rotational speed as high as 235 rpm, which corresponded with the experimental results. Furthermore, the simulation results accurately predicted the fraction of microorganism remaining when the ambient air exchange rate was 2 ACH. We conclude that this novel numerical model can reproduce the effects of ceiling fans and UR-UVGI fixtures on indoor environment, and should aid in the investigation of the impact of ceiling fans on UR-UVGI disinfection efficacy.

Keywords
Airborne infection control Ceiling fan Computational fluid dynamics Fraction of microorganism remaining Upper-room ultraviolet germicidal irradiation
作者与单位
共 5 位作者,点击展开单位 / ORCID
Zhu Shengwei
School of Architecture and Urban Planning, Huazhong University of Science and Technology, Wuhan, Hubei, P. R. China.
Srebric Jelena
Department of Architectural Engineering, The Pennsylvania State University, State College, Pennsylvania, USA.
Rudnick Stephen N
Department of Environmental Health, Harvard School of Public Health, Boston, Massachusetts, USA.
Vincent Richard L
Mount Sinai School of Medicine, New York City, New York, USA.
Nardell Edward A
Department of Environmental Health, Harvard School of Public Health, Boston, Massachusetts, USA ; Brigham and Women's Hospital, Boston, Massachusetts, USA.
Article Info
Journal
Building and environment
Abbr.
Build Environ
ISSN
0360-1323
Published
2014-02-00
页码
116-124
Language
English
Country/Region
England
NLM ID
101562928
基金资助
FIC NIH HHS · R24 TW008821 · United States
Analysis Services
Analysis Services

Contact

No. 2 Wenbo Road, Zhangqiu District, Jinan, Shandong

Qilu Normal University · Genelibs Bioinformatics Lab

750 Shunhua Rd, Jinan

2F, Bldg F, University Science Park

Tel: 0531-88819269

WeChat Official Account

Follow our WeChat subscription account for real-time updates and the latest in medical and biological research.


Business Email

E-mail: [email protected]