Marrying Step Feed with Secondary Clarifier Improvements to Significantly Increase Peak Wet Weather Treatment Capacity: An Integrated Methodology.

Daigger GT, Siczka JS, Smith TF, Frank DA, McCorquodale JA

Abstract

The need to increase the peak wet weather secondary treatment capacity of the City of Akron, Ohio, Water Reclamation Facility (WRF) provided the opportunity to test an integrated methodology for maximizing the peak wet weather secondary treatment capacity of activated sludge systems. An initial investigation, consisting of process modeling of the secondary treatment system and computational fluid dynamics (CFD) analysis of the existing relatively shallow secondary clarifiers (3.3 and 3.7 m sidewater depth in 30.5 m diameter units), indicated that a significant increase in capacity from 416 000 to 684 000 m3/d or more was possible by adding step feed capabilities to the existing bioreactors and upgrading the existing secondary clarifiers. One of the six treatment units at the WRF was modified, and an extensive 2-year testing program was conducted to determine the total peak wet weather secondary treatment capacity achievable. The results demonstrated that a peak wet weather secondary treatment capacity approaching 974 000 m3/d is possible as long as secondary clarifier solids and hydraulic loadings could be separately controlled using the step feed capability provided. Excellent sludge settling characteristics are routinely experienced at the City of Akron WRF, raising concerns that the identified peak wet weather secondary treatment capacity could not be maintained should sludge settling characteristics deteriorate for some reason. Computational fluid dynamics analysis indicated that the impact of the deterioration of sludge settling characteristics could be mitigated and the identified peak wet weather secondary treatment capacity maintained by further use of the step feed capability provided to further reduce secondary clarifier solids loading rates at the identified high surface overflow rates. The results also demonstrated that effluent limits not only for total suspended solids (TSS) and five-day carbonaceous biochemical oxygen demand (cBOD5) could be maintained, but also for ammonia-nitrogen and total phosphorous (TP). Although hydraulic limitations in other parts of the WRP prevent this full capacity to be realized, the City is proceeding to implement the modifications identified using this integrated methodology.

MeSH 主题词
Drainage, Sanitary/methods Rain Waste Disposal Facilities Waste Disposal, Fluid/methods Water Movements Water Purification
作者与单位
共 5 位作者,点击展开单位 / ORCID
Daigger Glen T
Siczka John S
Smith Thomas F
Frank David A
McCorquodale J A
Article Info
Journal
Water environment research : a research publication of the Water Environment Federation
Abbr.
Water Environ Res
ISSN
1061-4303
Published
2017-08-01
电子出版
2017-00-22
页码
724-731
Language
English
Country/Region
United States
NLM ID
9886167
Analysis Services
Analysis Services

Contact

No. 2 Wenbo Road, Zhangqiu District, Jinan, Shandong

Qilu Normal University · Genelibs Bioinformatics Lab

750 Shunhua Rd, Jinan

2F, Bldg F, University Science Park

Tel: 0531-88819269

WeChat Official Account

Follow our WeChat subscription account for real-time updates and the latest in medical and biological research.


Business Email

E-mail: [email protected]