Home LiteratureArticle Details
PMID: 32288029 Published · ppublish English Journal Article

Potential airborne transmission between two isolation cubicles through a shared anteroom.

Building and environment ·Vol. 89 ·2015-07-00 ·页码 264-278

Hang J, Li Y, Ching WH, Wei J, Jin R, Liu L, Xie X

Abstract

Full-scale experiments and CFD simulations were performed to study potential inter-cubicle airborne transmissions through a shared anteroom due to the hinged door opening. When doors are closed, current negative pressure designs are effective for the containment of airborne pathogens in the 'dirty' cubicle with an index patient. When the 'dirty' cubicle door is open, airborne agents can move into the other 'clean' cubicle via the shared anteroom. As the door being opened or closed, the door sweeping effect is the main source of the two-way airflow and contaminant exchange through the doorway. When the dirty cubicle door remains fully open, temperature difference and concentration gradient across the doorway induce the two-way buoyancy-driven flow and transport of airborne agents across the doorway. The longer the dirty cubicle door remains fully open (10 s, 30 s or 60 s) or the smaller the air change rate (34-8.5 ACH for each cubicle), the more airborne pathogens are being transported into the 'clean' cubicle and the longer time it takes to remove them after the door is closed. Keeping the door completely open is potentially responsible for the majority of inter-cubicle transmissions if its duration is much longer than the duration of door motion (only 3 s). Our analyses suggest a potential inter-cubicle infection risk if the shared anteroom is used for multiple isolation cubicles. Decreasing the duration of door opening, raising air change rate or using a curtain at the doorway are recommended to reduce inter-cubicle exposure hazards.

Keywords
Computational fluid dynamic (CFD) simulation Door motion Full-scale field experiment Inter-cubicle airborne transmission Isolation room
作者与单位
共 7 位作者,点击展开单位 / ORCID
Hang Jian
Department of Atmospheric Sciences, School of Environmental Science and Engineering, Sun Yat-Sen University, Guangzhou, PR China.
Li Yuguo
Department of Mechanical Engineering, The University of Hong Kong, Hong Kong.
Ching W H
Energy Services, CLP Engineering Limited, Hong Kong.
Wei Jianjian
Department of Mechanical Engineering, The University of Hong Kong, Hong Kong.
Jin Ruiqiu
Department of Atmospheric Sciences, School of Environmental Science and Engineering, Sun Yat-Sen University, Guangzhou, PR China.
Liu Li
Department of Civil Engineering, Alborg University, Denmark.
Xie Xiaojian
Jiangsu Provincial Key Laboratory of Materials Cycling and Pollution Control, School of Energy and Mechanical Engineering, Nanjing Normal University, Nanjing, PR China.
Article Info
Journal
Building and environment
Abbr.
Build Environ
ISSN
0360-1323
Published
2015-07-00
电子出版
2015-00-13
页码
264-278
Language
English
Country/Region
England
NLM ID
101562928
Analysis Services
Analysis Services

Contact

No. 2 Wenbo Road, Zhangqiu District, Jinan, Shandong

Qilu Normal University · Genelibs Bioinformatics Lab

750 Shunhua Rd, Jinan

2F, Bldg F, University Science Park

Tel: 0531-88819269

WeChat Official Account

Follow our WeChat subscription account for real-time updates and the latest in medical and biological research.


Business Email

E-mail: [email protected]