Home LiteratureArticle Details
PMID: 33229090 Published · ppublish English Journal Article

Sensitivity analysis of influence factors on multi-zone indoor airflow CFD simulation.

The Science of the total environment ·Vol. 761 ·2021-03-20 ·页码 143298

Cheng JCP, Kwok HHL, Li ATY, Tong JCK, Lau AKH

Abstract

Computational fluid dynamics (CFD) is a powerful tool for performing indoor airflow analysis. The simulation results are usually validated with measurement results for accuracy in reflecting reality. When conducting CFD for simulating air flow in a multiple-zone indoor environment with different boundary conditions in different regions, the validation of the CFD model becomes sophisticated. To improve the accuracy of the simulation, boundary conditions need to be adjusted based on how significant the influence factors are affecting the multi-zone CFD model, which few studies have been conducted on. The objective of this study is to investigate the impact of influence factors on temperature and carbon dioxide concentration distribution of a validated CFD model of a typical office floor using ANSYS Fluent. This study provides insights on how to fine-tune a complex model to reflect the actual air flow and how the air quality and human comfort in different zones on the same floor could be affected by influence factors. The influence factors investigated are: (1) size of door gaps, (2) solar radiation and (3) number and orientation of occupants. The velocity variations caused by different door gap sizes were studied for improving multi-zone simulation accuracy by adjusting door gap sizes. To study the significant impact of solar heat on multi-zone environment, the sensitivity of different regions of the office floor to solar heat amount and distribution was analyzed by conducting solar analysis under different weather conditions. Impact of occupants on temperature and carbon dioxide concentration distributions in multi-zone environment were investigated by considering different numbers and facing directions of occupants in different regions of the office floor. In addition, this study demonstrates how to modify the influence factors efficiently using building information modeling (BIM).

Keywords
Building information modeling Computational fluid dynamics Indoor air quality Indoor partition Solar analysis Thermal comfort
作者与单位
共 5 位作者,点击展开单位 / ORCID
Cheng Jack C P
Department of Civil and Environmental Engineering, Hong Kong University of Science and Technology, Clear Water Bay, Kowloon, Hong Kong. Electronic address: [email protected].
Kwok Helen H L
Department of Civil and Environmental Engineering, Hong Kong University of Science and Technology, Clear Water Bay, Kowloon, Hong Kong. Electronic address: [email protected].
Li Alison T Y
Division of Environment and Sustainability, Hong Kong University of Science and Technology, Clear Water Bay, Kowloon, Hong Kong. Electronic address: [email protected].
Tong Jimmy C K
Ove Arup & Partners Hong Kong Ltd, Level 5 Festival Walk, 80 Tat Chee Avenue, Kowloon Tong, Kowloon, Hong Kong. Electronic address: [email protected].
Lau Alexis K H
Division of Environment and Sustainability, Hong Kong University of Science and Technology, Clear Water Bay, Kowloon, Hong Kong. Electronic address: [email protected].
Article Info
Journal
The Science of the total environment
Abbr.
Sci Total Environ
ISSN
1879-1026
Published
2021-03-20
电子出版
2020-00-04
页码
143298
Language
English
Country/Region
Netherlands
NLM ID
0330500
Analysis Services
Analysis Services

Contact

No. 2 Wenbo Road, Zhangqiu District, Jinan, Shandong

Qilu Normal University · Genelibs Bioinformatics Lab

750 Shunhua Rd, Jinan

2F, Bldg F, University Science Park

Tel: 0531-88819269

WeChat Official Account

Follow our WeChat subscription account for real-time updates and the latest in medical and biological research.


Business Email

E-mail: [email protected]