Influence of pallet height on energy consumption and cooling effectiveness in an apple cold storage.

Scientific reports ·Vol. 15 ·No. 1 ·2025-04-04 ·页码 11534

Alexander LD, Jakhar S, Dasgupta MS

Abstract

This study investigates the influence of pallet height on energy consumption and cooling effectiveness using a validated cold storage model based on CFD simulations. The model was validated against experimental temperature data, with a maximum normalized root mean square error (NRMSE) of 4.57%, indicating good agreement. Four pallet height configurations namely No pallet (0.0 m), 0.3 m, 0.6 m, and 0.9 m were assessed over a 40-hour cooling period. Temperature distribution within apple-filled crates was used to identify the locations of hot and cold spots, and performance metrics such as compressor energy consumption, specific energy consumption, mean crate temperature, thermal heterogeneity, and cooling effectiveness were analyzed. The results indicate that the No-pallet configuration disrupts airflow resulting in insufficient cooling, as evidenced by lower cooling effectiveness, while larger pallet heights (0.6 m and 0.9 m) introduce excessive air spacing resulting in higher thermal heterogeneity. The 0.3 m pallet height exhibited best performance such as lowest mean crate temperature of 4.7 °C, (8.7% lower), lowest thermal heterogeneity of 3.29 (14.42% lower), lowest compressor energy consumption per kelvin of 1.474 kWh/K (0.5% lower) and highest cooling effectiveness of 0.4 (5.37% higher). These findings provide practical insights for optimizing pallet configurations in cold storage, aiding energy-efficient operations in commercial refrigerated warehouses and post-harvest supply chains.

Keywords
Cold storage Computational fluid dynamics Porous medium Post harvest Thermal heterogeneity
作者与单位
共 3 位作者,点击展开单位 / ORCID
Alexander Leo Daniel
Smart Building Laboratory, Department of Mechanical Engineering, Birla Institute of Technology & Science, Pilani, Rajasthan, 333031, India. [email protected].
Jakhar Sanjeev
School of Mechanical Engineering, Vellore Institute of Technology, Chennai, 600127, Tamil Nadu, India. [email protected].
Dasgupta Mani Sankar
Smart Building Laboratory, Department of Mechanical Engineering, Birla Institute of Technology & Science, Pilani, Rajasthan, 333031, India.
Article Info
Journal
Scientific reports
Abbr.
Sci Rep
ISSN
2045-2322
Published
2025-04-04
电子出版
2025-00-04
页码
11534
Language
English
Country/Region
England
NLM ID
101563288
Analysis Services
Analysis Services

Contact

No. 2 Wenbo Road, Zhangqiu District, Jinan, Shandong

Qilu Normal University · Genelibs Bioinformatics Lab

750 Shunhua Rd, Jinan

2F, Bldg F, University Science Park

Tel: 0531-88819269

WeChat Official Account

Follow our WeChat subscription account for real-time updates and the latest in medical and biological research.


Business Email

E-mail: [email protected]