Performance evaluation of a recirculated personalized air curtain combined with displacement ventilation in mitigating indoor airborne transmission.

Journal of hazardous materials ·Vol. 494 ·2025-08-15 ·页码 138446

Xu J, Zhai H, So LK, Wang C, Guo H

Abstract

To mitigate the risk of airborne transmission, we explored the integration of a recirculated personalized air curtain (rPAC) with displacement ventilation (DV) using computational fluid dynamics (CFD) simulations. The rPAC can utilize indoor air directly, drawing clean air from the lower room space supplied by the DV system. Our study assessed the effectiveness of the rPAC in reducing the intake fraction of expiratory droplets from transient coughing and steady speaking indoors. We categorized droplets into small (initial diameter ≤20 μm), medium (50 μm), and large (100 μm) sizes. Large droplets from both activities generally had negligible intake fractions. The rPAC effectively reduced the intake fraction from coughing and speaking, although its performance varied with respiratory activities and exhalation directions. At 0° and 30°, the rPAC reduced the intake fraction of small coughing droplets by over 90 % and medium droplets by 74 %-98 %, with significant reductions also observed for speaking. However, at 60°, the rPAC increased the intake fraction of medium coughing droplets and small droplets from speaking due to complex airflow-droplet interaction dynamics. This study highlights the potential of rPAC as an effective control measure to improve indoor air quality and mitigate respiratory disease transmission, though its effectiveness is influenced by exhalation direction and droplet size.

Keywords
Airborne transmission Exposure Protection Recirculated personalized air curtain Respiratory diseases
MeSH 主题词
Air Pollution, Indoor/prevention & control Ventilation/methods Humans Cough Hydrodynamics COVID-19/transmission,prevention & control
作者与单位
共 5 位作者,点击展开单位 / ORCID
Xu Jingcui
Air Quality Studies, Department of Civil and Environmental Engineering, The Hong Kong Polytechnic University, Hong Kong.
Zhai Haoyu
Air Quality Studies, Department of Civil and Environmental Engineering, The Hong Kong Polytechnic University, Hong Kong.
So Lok Kwan
Air Quality Studies, Department of Civil and Environmental Engineering, The Hong Kong Polytechnic University, Hong Kong.
Wang Cunteng
Air Quality Studies, Department of Civil and Environmental Engineering, The Hong Kong Polytechnic University, Hong Kong.
Guo Hai
Air Quality Studies, Department of Civil and Environmental Engineering, The Hong Kong Polytechnic University, Hong Kong. Electronic address: [email protected].
Article Info
Journal
Journal of hazardous materials
Abbr.
J Hazard Mater
ISSN
1873-3336
Corresponding email
Published
2025-08-15
电子出版
2025-00-29
页码
138446
Language
English
Country/Region
Netherlands
NLM ID
9422688
Analysis Services
Analysis Services

Contact

No. 2 Wenbo Road, Zhangqiu District, Jinan, Shandong

Qilu Normal University · Genelibs Bioinformatics Lab

750 Shunhua Rd, Jinan

2F, Bldg F, University Science Park

Tel: 0531-88819269

WeChat Official Account

Follow our WeChat subscription account for real-time updates and the latest in medical and biological research.


Business Email

E-mail: [email protected]