Abstract
Fourteen recirculating cooling water systems were surveyed during the summer, 1981, to see what factors might influence the prevalence of Legionella pneumophila. The effect on the organism of three anti-microbials was studied, each in two systems, by intermittent treatment at two week intervals. L. pneumophila was isolated from six of the 14 cooling systems at the beginning of the trial but by the end was present in ten. An association was found between the presence of the organism and the concentration of dissolved solids, and chlorides and the pH. There also appeared to be associations with exclusion of light and higher water temperatures. Repeated tests on eight untreated systems showed that two were consistently infected, three became and remained infected, one was infected on a single occasion and two were never infected with L. pneumophila. Treatment of a contaminated system, either with a 10 p.p.m mixture of a quaternary ammonium compound and tributyltinoxide or slow release chlorine briquettes (maximum recorded free chlorine level 1.2 p.p.m.), did not eliminated legionellae. Treatment of two infected towers with a chlorinated phenol (100 p.p.m.) eliminated legionellae for at least three days, but after 14 days the organism was again found.
MeSH Terms
Air Conditioning
Chlorides/pharmacology
Chlorine/pharmacology
Chlorophenols/pharmacology
Disinfectants/pharmacology
Hydrogen-Ion Concentration
Legionella/growth & development
London
Quaternary Ammonium Compounds/pharmacology
Temperature
Time Factors
Trialkyltin Compounds/pharmacology
Water Microbiology
Chemicals
Chlorides
Chlorophenols
Disinfectants
Quaternary Ammonium Compounds
Trialkyltin Compounds
bis(tri-n-butyltin)oxide
Chlorine
Authors & Affiliations
5 authors, click to expand affiliations / ORCID
Kurtz J B
Bartlett C L
Newton U A
White R A
Jones N L
References (14)
14 references, click to expand
-
Growth, survival, and resistance of the Legionnaires' disease bacterium.
Ann Intern Med. 1979 Apr;90(4):614-8
PMID: 571258
-
Isolation of the Legionnaires' disease bacterium from environmental samples.
Ann Intern Med. 1979 Apr;90(4):664-6
PMID: 373549
-
Isolation of Legionella pneumophila from nonepidemic-related aquatic habitats.
Appl Environ Microbiol. 1979 Jun;37(6):1239-42
PMID: 384910
-
An outbreak of Legionnaires' disease associated with a contaminated air-conditioning cooling tower.
N Engl J Med. 1980 Feb 14;302(7):365-70
PMID: 7351928
-
Growth of Legionella pneumophila in association with blue-green algae (cyanobacteria).
Appl Environ Microbiol. 1980 Feb;39(2):456-9
PMID: 6769388
-
Pittsburgh pneumonia agent: direct isolation from human lung tissue.
J Infect Dis. 1980 Jun;141(6):727-32
PMID: 7391615
-
Laboratory studies of disinfectants against Legionella pneumophila.
Appl Environ Microbiol. 1980 Oct;40(4):697-700
PMID: 6252840
-
Preliminary report on the pathogenicity of Legionella pneumophila for freshwater and soil amoebae.
J Clin Pathol. 1980 Dec;33(12):1179-83
PMID: 7451664
-
Isolation of Legionella pneumophila from water systems: methods and preliminary results.
Br Med J (Clin Res Ed). 1981 Feb 14;282(6263):515-7
PMID: 6780104
-
Isolation of Legionella pneumophila from hospital shower heads.
Ann Intern Med. 1981 Feb;94(2):195-7
PMID: 7469211
-
Susceptibility of Legionella pneumophila to three cooling tower microbicides.
Appl Environ Microbiol. 1981 Jan;41(1):233-6
PMID: 7224623
-
Ecological distribution of Legionella pneumophila.
Appl Environ Microbiol. 1981 Jan;41(1):9-16
PMID: 7013702
-
Epidemic Legionnaires' disease. Airborne transmission down a chimney.
JAMA. 1981 Jun 19;245(23):2404-7
PMID: 7230470
-
Investigation and control of an outbreaks of legionnaires' disease in a district general hospital.
Lancet. 1981 Apr 25;1(8226):932-6
PMID: 6112337